TX10 pH/ORP Transmitter

TX10 - pH/ORP Transmitter, 4-20mA

TX10 pH/ORP Transmitter

R11,770.00 Excl. VAT

In stock

R11,770.00 Excl. VAT

The TX10 pH and ORP transmitter is a convenient and cost-effective solution for pH and ORP monitoring. This transmitter allows you to save space in your panel with the small footprint of its 1/8 DIN case. The isolated, reversible 4-20mA output of the transmitter provides versatility for a range of process control possibilities. Includes panel-mount brackets. Lead time is 4 weeks.

Availability: Available on backorder SKU: SE-TX10 Categories: ,
View cart

Description

TX10 pH/ORP Transmitter

This device has an isolated, reversible 4-20mA current output

The TX10 and TX20 transmitter series offer a cost-effective, small footprint solution for pH and ORP process control. Save space in your panel with either of these 1/8 DIN size models. The simple and easy-to-understand user interface features a four-button membrane keypad for quick setup and programming. The TX10 has an isolated, reversible 4-20mA current output, providing versatility for a wide range of process control applications. The TX20 features two sets of programmable on/off relays, allowing the device to control warning lights, alarms, or other process control systems. Both models feature a large, clear LCD panel for quick, easy reference of pH, ORP, or temperature. Range: -2.00 to 16.00 pH; -1999 to 1999 mV ORP.

Features

  • Easy to install 1/8 DIN Case
  • 4-20mA current output
  • Compatible with sensors that utilize spade lug connectors
  • Clear LCDs pH, ORP, and temperature
  • Universal power supply input from 100-240VAC
  • Automatic US and NIST buffer recognition
  • Two sets of programmable on/off relays (TX20)
  • Or isolated, reversible 4-20mA current output (TX10)

Note: The TX10 pH and ORP transmitter is only compatible with sensors that have spade lug connectors.

Specifications

  • Measurement Range (pH): -2.00 to 16.00pH, 0.01 pH resolution, +/- 0.1% accuracy
  • Measurement Range (ORP/mV): -1999mV to 1999mV, 1mV resolution, +/- 0.1% accuracy
  • Temperature Range: -10 °C to 120 °C , 0.1 °C resolution, +/- 0.3 °C accuracy
  • Current Output Range/Scale: 4-20mA (isolated) / Linear
  • Enclosure: 1/8 DIN (3.78″ L x 3.54″ W x 1.89″ H)
  • Ambient Operating Temperature: 0° C to 50° C
  • Temperature Compensation: Auto/Manual (-10 °C to 120 °C)
  • Power Requirement: 100-240 VAC, max 500 ohm load
  • Weight: 290g

Additional information

Weight 1 kg